acr FLW_LOGO
Other Sites   |   Sitemap
power watch
.
PowerWatch
Plug-style Voltage Disturbance Recorder
ACR PowerWatch logger records essential power quality events and disturbances. It provides safe, stand alone operation with no wires, alligator clips or other exposed wiring. With the capacity to record up to 4000 events and an optical alarm indicating events occurred, ACR PowerWatch is the easiest way to monitor and record essential voltage disturbance information.
 
Software: See Software
Specification: See Common Specification

PW 120V

PW 220/240V

 

120V Voltage Disturbance Recorder

Frequency Range: 45 to 65 Hz.
Frequency Resolution: 0.1 Hz.
Frequency Accuracy: +/-0.1 Hz. (3 cycles minimum)
Memory Size: 4,000 events.
Software: See Software
Product Specification: See Product Specification
Surge, Sag & Outage Hot to Neutral Neutral to Ground
Range 0 to 200 V rms 3 to 200 V rms
Accuracy +/-1 V rms + resolution +/-1 V rms + resolution
Resolution: 1 V rms 1 V rms
Impulse Hot to Neutral Neutral to Ground
Range: 100 to 2500 V peak 50 to 2500 V peak
Accuracy: +/-10% of reading + resolution +/-10% of reading + resolution
Resolution: 10 V 10 V
Width Detection: 1 msec minimum 1 msec minimum
Phase Angle Accuracy: +/-1° (20 to 180°, 200 to 360°) +/-1° 20 to 180°, 200 to 360°)
Phase Angle Resolution:
Time Events (<1 sec) Hot to Neutral Neutral to Ground
Accuracy: +/-0.5 cycle +/-1 cycle
Resolution: 0.5 cycle 1 cycle
Time-stamp Accuracy: +/-2 sec./day + resolution
Time-stamp Resolution: 8 seconds

catalog #

$640.00

 

220/240V, 50/60 Hz Voltage Disturbance Recorder

Frequency Range: 45 to 65 Hz.
Frequency Resolution: 0.1 Hz.
Frequency Accuracy: +/-0.1 Hz. (3 cycles minimum)
Memory Size: 4,000 events.
Software: See Software
Product Specification: See Product Specification
Surge, Sag & Outage Hot to Neutral Neutral to Ground
Range 0 to 400 V rms 0 to 50 V rms
Accuracy +/-2 V rms + resolution +/-.25 V rms + resolution
Resolution: 2 V rms .25 V rms
Impulse Hot to Neutral Neutral to Ground
Range: 100 to 2500 V peak 50 to 2500 V peak
Accuracy: +/-10% of reading + resolution +/-10% of reading + resolution
Resolution: 10 V 10 V
Width Detection: 1 msec minimum 1 msec minimum
Phase Angle Accuracy: +/-1° (20 to 180°, 200 to 360°) +/-1° (20 to 180°, 00 to 360°)
Phase Angle Resolution:
Time Events (<1 sec) Hot to Neutral Neutral to Ground
Accuracy: +/-0.5 cycle +/-1 cycle
Resolution: 0.5 cycle 1 cycle
Time-stamp Accuracy: +/-2 sec./day + resolution
Time-stamp Resolution: 8 seconds

catalog #

$640.00

 

(800) 576-6308 or email for Application Assistance    

Storage Method: First-in, First-out or Fill-then-stop.
Size: 85 mm x 68 mm x 35 mm. (3.35" x 2.65" x 1.35").
Weight: 4 ounces (120 grams).
Case Material: Noryl® Plastic.
Operating Limits: 40°C to 70°C (-40°F to 158°F); 0 to 95% RH (non-condensing).
Battery: 3.6 Volt Lithium.
Battery Life: 10-years warrantied (under normal use). Factory replaceable.
Memory Size: 32 K, 4000 events.
Sampling Method: Continuous (half cycle integrated).
Alarm Type: Optical; Red LED.
PDF Click Here
Fuse: 1/16A fast-blow; (non-replaceable).
PC Requirements: IBM PC or 100% compatible running MS Windows 3.1,95,98, or NT, with a least 2 MB RAM, 2 MB of hard drive disk space and one free serial port.
Certifications: CSA; NRTL/C; UL1244.
Event Types Detected: Surges, sags, impulses, dropouts, outages, frequency variations.
Measurement Locations: Hot to Neutral. Neutral to Ground.
Plug Configurations: North America (120 Volt). Australia (240 Volt). United Kingdom (240 Volt). Continental Europe (240 Volt).

 

 