The Dwyer Series 2200 Current to Pressure Transducer combines low cost, accuracy and minimal air consumption with field-proven technology. Versatile design features a rugged, compact housing with a choice of FM approved explosion-proof or intrinsically safe operation when used with a suitable barrier. This transducer utilizes a practically weightless membrane that is electromagnetically positioned over the air flow, consuming minimal air and electrical energy while providing an accurate, precise output pressure signal. This low-mass membrane yields an output that is virtually unaffected by shock, vibration or mounting position. By employing an internal feedback network, the I/P responds quickly to step input changes, and by balancing air supply and exhaust, provides control stability while delivering accuracies of ±0.15%. The pneumatic control signal is enhances by an internal volume booster. The unit features easy access to zero and span adjustments, plus controls for field selectable direct, reverse or split-range operation.
| Model Number | Input | Output | Housing |
|---|---|---|---|
| 2213-0 2216-0 2213-0-E 2216-0-E |
4-20 mA 4-20 mA 4-20 mA 4-20 mA |
3-15 psig 6-30 psig 3-15 psig 6-30 psig |
Intrinsically Safe Intrinsically Safe Explosion-Proof Explosion-Proof |
| Output: | 3-15 psig (.21-1.1 kg/cm2), 6-30 psig (.42-2.1 kg/cm2) |
|---|---|
| Supply: | 20 (±2) psig for 3-15 psig; 1.4 (±0.14) kg/cm2 for 0.21-1.1 kg/cm2 output 35 (±2) psig for 6-30 psig: 2.5 (±0.14) kg/cm2 for 0.42-2.1 kg/cm2 output |
| Connection: | 1/4" NPTF supply port (1) and 1/4" NPTF output port (2). 1/2" NPTF electrical conduit connection |
| Output Capacity: | 4.0 scfm (1.9 I/s) |
| Air Consumption: | 0.04 scfm (.02 I/s) steady state average; 0.06 scfm (.031 I/s) maximum |
| Operational Mode: | Direct, reverse, and/or split range (field- selectable) |
| Failure Mode: | Transducer always fails in the direct mode (i.e., if input current drops below 3.7 mA DC the output will drop to 1 to 2 psig regardless of direct or reverse mode selection) |
| Enclosure: | internally purged NEMA 4X cast/machined aluminum with powder coat epoxy |
| Weight: | 2.5 lbs. (1.13kg) |
| ELECTRICAL | |
| Input: | 4-20 mA |
| Operating current: | 3.7 mA minimum, 200 mA maximum |
| PERFORMANCE | |
| Accuracy: | ±0.15% of span (3-15 psig, 0.21-1.1 kg/cm2) ±0.25% of span (6-30 psig. 0.42-2.1 kg/cm2) |
| Repeatability: | 0.05% of span |
| Deadband: | 0.02% of span |
| Stability: | 0.5% of span/6 months |
| Vibration Effect: | less than 0.25% from 1-200 Hz/1g |
| Frequency Response: | -3db at 5 Hz |
| Loop Load: | 3.8 VDC +5 ohms (195 ohm load at 20 mA) |
| Operating Temperature: | -20 to 150°F (-29 to 66°C) |
| Temperature Effect: | less than 1% per 100°F (55°C) |
| RFI-EMI Effect: | per SAMA PMC 33.1 standard (b), (c) 20 to 100 MHz, Class 3 effect on zero & span less than 1% |
APPLICATIONS
This transducer provides an excellent interface between Dwyer Temperature Controllers, Models 1600 or 2500 and the Hi-Flow™ Valve for such industries as food and beverage processing, chemical, pharmaceutical and wood pulp and paper. It can be factory mounted and calibrated to Hi-Flow™ Pneumatic Control Valves at no extra charge.
SUGGESTED SPECIFICATIONS
Current to pressure transducer shall be FM approved for (intrinsically safe) (explosion-proof) operation with ±0.15% accuracy. Input shall be 4-20 mA with 3-15 psi output, capable of field selectable modes of direct, reverse or split range. Air consumption shall be 0.04 scfm average for steady state with 0.06 scfm maximum. Transducer shall be Dwyer Instruments, Inc. Model No. 22__ __-__-__.