Back To Previous PagePHONE NUMBER
Sitemap

Diaphragm Operated Pressure Switches- Series 1000

Visible setpoint, fixed deadband, pressure ranges to 1400 PSI.

Series 1000 Series 1000

Same rugged construction as used in Model 1000W plus explosion-proof design are combined in this new unit. UL listed for Class I, Groups A, B, C & D; Class II, Groups E, F, & G. Bellville Spring Movement permits mounting of control in any position and helps prevent contact chatter. High over-pressure protection and vibration resistance are also featured.

PHYSICAL DATA



Maximum Temperature: 170°F (76°C)
Pressure Connection: ¼" NPT female
Electrical Ratings: 1/8 HP, 12A @ 125 VAC resistive; ¼ HP, 12A @ 250 VAC resistive; 0.5A @ 125 VCD resistive
Wiring Connections: Three Screw type; N.o., N.C. and Common
Setpoint Adjustment: Internal thumbwheel with visible scale
Housing: Die cast copper free aluminum - weatherproof
Diaphragm: Polyimide, Teflon® or 316 stainless steel
Calibration Spring: Plated Steel
Mounting: 4 holes to accept 1/4" bolts
Weight: 3 lbs. (1.4 kg)
Installation: Any position

FACTORY STOCKED MODELS



Aluminum Pressure
Chamber
Polymide Diaph.
Model Number
316 Stainless Steel
Pressure Chamber
Teflon Diaphragm
Model Number
Adjustable
Operating
Range
PSIG
Approx.*
Deadband
(Fixed)
PSIG
Maximum
Pressure
1003W-A1-D
1004W-A1-D
1005W-A1-D
1006W-A1-D
1007W-A1-D
1008W-A1-D
1009W-A1-D
1003W-B3-D
1004W-B3-D
1005W-B3-D
1006W-B3-D
1007W-B3-D
1008W-B3-D
1009W-B3-D
7-40
10-70
25-200
50-350
75-550
100-900
200-1400
2
4
8
15
30
50
75
600 psig
3000 psig
3000 psig
3000 psig
3000 psig
3000 psig
3000 psig
*Deadband 10-15% larger when using 316SS diaphragm. Change A1 to B2 for 316 stainless steel diaphragm
and pressure chamber e.g. 1003E-B2-J. Values shown are for mid-scale.

Suggested Specifications
Pressure switches shall be diaphragm operated with fully adjustable set point. They shall be weatherproof and explosion-proof. Switches shall have visible set point indicator protected by clear polycarbonate window. Switches shall have 18" leads to be field connected and sealed. Units shall be Mercoid Model 100 (___) E(___).

- © FLW, Inc 1997- - S.D.G.