Back To Previous PagePHONE NUMBER
Sitemap

Process Signal Converter/Isolator- Model 4380

Converts Process Signal, Isolated to 1500 V RMS.

Model4380

The Iso-Verter®II Isolator/Converter protects electronic circuits by completely isolating the input and output signals from each other and from ground. Both input and output ranges are fully field selectable with easy to adjust switches. With bipolar input selection and zero suppression, nearly any standard input/output range combination is possible. Zero and span adjustments are easily accessible on top of housing. Units plug into universally available octal sockets for quick easy installation. Industry standard "pin-out" wiring configuration allows direct replacement of most competitive models. Order optional 481-0159 socket for new installations.

RANGES AVAILABLE (Field Selectable)



Inputs Outputs
Current Voltage Current Voltage
0-5 mA
0-10 mA
0-20 mA
0-50 mA
0-100 mA
1-5 mA
4-20 mA
10-50 mA
0-100V
0-200V
0-500V
0-1V
0-5V
0-10V
1-5V
2-10V
0-1 mA
0-5 mA
0-20 mA
1-5 mA
4-20 mA
0-1V
0-5V
0-10V
1-5V
2-10V

PHYSICAL DATA.



Isolation: 1500 VAC
Linearity: 0.1% of full span
Drift: ±0.02%/°C typical; ±0.05%°C maximum
Ambient Operating Temperature: 32 to 131°F (0 to 55°C)
Output Loads: Current: 600 ohms maximum
Voltage: 500 ohms minimum (20 mA maximum)
Input Impedance: Current: 10 ohms, Voltage: 1 megohm
Power Supply: 85-265 VDC/VAC, 50-400 Hz
Case Size: (including socket pins)
2 3/8"W x 3 7/16"H x 1 ¾"D
60.3 mm W x 87.3mm H x 44.4 mm D
Height is 2 7/8" (73 mm) above socket
Mounting: Industry standard octal socket

- © FLW, Inc 1997- - S.D.G.