Continuously monitor the levelof liquids and slurries, without worry of false signals as a result of material build-up. Loop powered Series CRF delivers a 4-20 mA isolated output signal proportional to the height of material in a tank or holding vessel. Continuous level transmitter can be field calibrated to fit your specific application. Integral electronics and two-wire design simplify installation. Probes should be mounted vertically and are easily trimmed to shorter lengths where required. When mounting in nonmetallic or horizontal tanks, a separate grounding rod must be used. Consult factory regarding mounting flange and grounding rod assemblies.

PHYSICAL DATA.
Supply Voltage: 18 to 30 VDC
Output Signal: 4-20 mA, 2-wire, isolated
Maximum Loop Resistance: 600W @ 24 VDC
Zero Range: 0 to 500 pF
Repeatability: 0.1% FS
Operating Temperature Range: -10 to 180°F (-23 to 82°C)
Mounting: ¾" NPT(M), Optional flange mounting
Conduit Opening: ½" NPT (F)
Probe Enclosure: NEMA 4, 7 & 9, epoxy coated aluminum
Wetted Materials: 316SS, Teflon®
Power Consumption: 6VA
Span Range: 25 to 2200 pF
Linearity: 0.3% of range
Weight: 7.25 lbs. (3.29 kg)
Model Number Description
CRF106000
CRF108000
Teflon® coated 316SS probe, 6 ft. length
Teflon® coated 316SS probe, 8 ft. length

APPLICATIONS Alcohols, wastewater, oils, polymers, acids, caustics, pulp, slurries, wood chips, water-based products in tanks, bins, or other vessels.

SUGGESTED SPECIFICATIONS
Level control transmitter shall provide a 4-20 mA isolated output signal for continuous monitoring of liquids and slurries. Probe enclosure shall be epoxy coated aluminum and meet NEMA 4, 7 & 9 ratings. Wetted parts shall be 316SS and Teflon®. Transmitter shall be Proximity Model CRF ____.