Back To Previous PagePHONE NUMBER
Sitemap

Pneumatic Positioners-Series 150N

Low Cost, Field Selectabe Cam Design

Series 150NSeries 150N

W.E. Anderson Series 150N Pneumatic Positioners deliver stable process control at an exceptionally low price. This versatile unit is cam characterized which allows use of a single internal range spring for all control spans. Rotation of the cam allows split range applications to be easily selected. Its rugged, durable design makes it ideal for use in harsh environments while maintaining precise, accurate positioning of the control element. This multi-faceted positioner requires no additional parts to convert from direct to reverse acting. Readily accessible zero and span adjustments are conveniently located behind a removable housing cover.

PHYSICAL DATA.

Connection: 1/8" NPT
Input: 3-15 psig (.21-1.1 kg/cm2), 3-27 psig (.21-1.9 kg/cm2)
Supply: 30 psig (2.1 kg/cm2) minimum; 150 psig (10.5 kg/cm2) maximum
Supply Pressure Change effect: output pressure changes less than 0.3% of span for a 5 psig (.35 kg/cm2) change
Air Consumption: 0.7 scfm (.33 I/s) at 60 psig (4.22 kg/cm2) supply Air Pilot Capacity: 7.5 scfm (3.5 I/s) at 60 psig (4.22 kg/cm2) supply
Adjustable Range: ±30% of input span or maximum rated travel
Stroke: Rectilinear, 1/2" to 2"
Temperature Units: -40°F to 180°F (-40°C to 82°C)
Weight: 2.5 lbs. (1.13 kg)
PERFORMANCE  
Repeatability: 0.1% of span.
Linearity: ± 1% of span.
Hysteresis: less than 0.75% of span.
Dead Band: less than 0.1% of span.
Response Level: less than 0.1% of span


FACTORY STOCKED MODELS

Model Number Input
150NL11- 3-15 psig
150NL12- 3-27 psig

How to Order:
  1. Select Model No. to specify pneumatic input control signal.
  2. For proper mounting hardware, specify which actuator the positioner will be mounted to.
(-220, -221, -222, -223)
LIN-E-AIRE® Air-To-Lower Actuators
(-230, -231, -233)
LIN-E-AIRE® Air-To-Raise Actuators

EXAMPLE: For a 3-15 PSI Control System utilizing a Hi-Flow™ Valve with LIN-E-AIRE® Actuator Model No. 2004VA32-223-A*, order Model No. 150NL11-223.

*Suffix -A is added to Hi-Flow™ Valve Model No. if Pneumatic Positioner is to be factory mounted and calibrated.

APPLICATIONS
This low-cost alternative to the Precisorâ Pneumatic Positioner provides excellent modulating control when used between the Dwyer Temperature Controllers (models 1600 or 2500), Current to Pressure Transducer (Model 2200 and the Hi-Flow™ Valve in such industries as the food and beverage processing, chemical, pharmaceutical, and wood pulp and paper.

SUGGESTED SPECIFICATIONS
Pneumatic Positioner shall be cam characterized, double-acting with 0.1% repeatability. The unit shall accept an input of 3-15 psig or 3-27 psig with capability of field-selectable modes of direct, reverse or split range operation. Supply pressure shall be capable of 150 psig maximum. Unit shall be W.E. Anderson Series 150N.