Reliably measure low pressures with Series 607 Differential Pressure Transmitters featuring ±0.25% accuracy. The transmitter utilizes a variable capacitance sensor to deliver exceptional sensitivity and stability. Series 607 transmitters are ideal for use with air or compatible gases in clean rooms, fume hoods, HVAC, and laboratory monitoring. Certification to NIST standards are included with each unit.
| Accuracy: | ±0.25% full scale @ 70°F (21°C), (includes linearity, hysteresis, and repeatability) |
| Service: | Air and nonconductive, noncorrosive gases |
| Output: | 4 to 20 mA DC, 2-wire |
| Supply Voltage: | 13-36 VDC, unregulated |
| Loop Resistance: | 0 to 1045 ohms Vmin.= 13V+ [(.22A)(R_) |
| Current Consumption: | 3.6 mA (min.) |
| Maximum Pressure: | 10 psig (0.7 kg/cm²) |
| Compensated Temperature Range: | 35 50 135°F (2 to 57°C) |
| Operating Temperature Range: | -20 to 160°F (-29 to 71°C), 10 to 95% RH |
| Thermal Effects: | ±0.015% %S/°F (zero and span) |
| Response Time: | 250 msec max. |
| Housing: | NEMA 2 stainless steel |
| Process Connection: | 4" barbed, stainless steel |
| Weight: | 14 oz (397 g) |
| Model Number | Range | Model Number | Range | |
| 607-01607-11 | 0 to 0.10" w.c.0 to 0.25" w.c. | 607-21607-71 | 0 to 0.50" w.c.0 to 0.5.0" w.c. |
SUGGESTED SPECIFICATIONS
Differential pressure transmitters shall employ a (piezoresistive - 606,606B)(variable capacitance - 607) transducer with micro-machined silicon diaphragm. Electrical signal shall be conditioned to a (3 wire-606)(2 wire-606B, 607) 4-20 mA output. Units shall be factory calibrated to (±1% - 606, 606B)(±0/5% - 607)F.S.O. with (zero - 606, 606B)(zero & span - 607) controls for field adjustment. Tranmitters shall be Dwyer Instruments, Inc. Catalog No. (606)(606B)(607)-___for the required operating ranges.