Back To Previous PagePHONE NUMBER
Sitemap

Quick Scan Recorders- Series 1300/1400

Electrical or Pneumatic Inputs, 0.5% Accuracy

Series 1300/1400
  • Records up to Four Inputs
  • Selectable Chart Speeds
  • Two-Speed Chart Drive Option
  • Low or High Alarm and/or Servo Locking Available
  • Transmitter Power Supply Available for Each Pen
  • Selectable Power Supply
Series 1300/1400

Love Quick Scanâ Recorders are capable of receiving and recording up to four process variable signals on a 4-inch strip chart. Each recording circuit is an independent self-balancing system. input voltages or pressures can be selected for the entire instrument or for each pen separately. The individual colored pens are supplied with ink from high capacity plastic capsules containing approximately a 6 month supply. Replacement is fast and easy from the front of the instrument.

Installation can be simplified by use of a Love mounting tray. All electrical connections are made to the tray so the instrument is quickly replaceable with no rewiring. With the recorder pulled partially out of its mounting tray, up to six hours of the chart record are visible through the window on the side. The chart moves within a removable cassette, simplifying loading.

Optional features include integral alarms, transmitter power supplies, and a servo locking feature. With servo locking, an integral timer blocks electrical power when the pen is at balance or pegged, reducing power consumption. Expandable mounting trays, sold separately, simplify installation and accommodate up to 10 instruments in a single panel cutout.

PHYSICAL DATA.

ELECTRICAL MODELS (1300)
Input Impedance: Greater than 1 megohm
Zero Limits: Continuously adjustable - 1V span: -0.5 to +0.5 VDC; 4V span: -2 to +2 VDC
Span Limits: Continuously adjustable - 1V span: 0.85 to 1.15 VDC; 4V span: 3.4 to 4.6 VDC
PNEUMATIC MODELS (1400):
Input: 3-15 psig (.21-1.03 bar)
Air Supply: Recommended, 22 psig (1.52 bar); Minimum, 19 psig (1.31 bar); Maximum, 26 psig (1.79 bar)
Air Consumption: 0.05 scfm/servo (0.08 m3/h/servo). Add 0.5 scfm (0.8 m3/h) for internal pneumatic chart drive.
Pen Response Time: 1 1/2 seconds full scale (electrical), 4 seconds full scale (pneumatic)
Alarm Contact Rating: (1300): 2A, 30 VAC rms; 2A, 42 VDC. (1400): 2A, 30 VDC; 125, 150 VAC.
Ambient Temperature Limits: Operating, 40 to 120°F (4.4 to 48.9°C). Storage, -40 to 165°F (-40 to 73.9°C).
Transmitter Power Supply (Optional): 24 VDC
Calibration Accuracy: +0.5% of span
Power Supply: Selectable from following: 110 VAC, 50 Hz;117 VAC (specify 50 or 60 Hz); 220 VAC, 50 Hz; 234 VAC, 50 Hz; 24-28 VDC
Weight: 12-18 lbs. (5.5-8.9 kg) approximate. Varies with model.

FACTORY STOCKED MODELS
Model No. (Electric) Model No. (Pneumatic) Size, In. No. Pens
1322J-A14100
1323J-A14100
1333J-A14100
1334J-A14100
1402J-A11100
1403J-A11100
1413J-A11100
1414J-A11100
6X3
6X3
6X6
6X6
2
3
3
4
Standard models include general purpose enclosure, 117 VAC, 60 Hz power, .25-1.25 VDC or 3-15 psig input (.21-1.1 kg/cm2) and 1 incl/hour chart speed. Consult factory for other available options.

- © FLW, Inc 1997- - S.D.G.