Differential Pressure Transmitters- Series 603A

4-20 mA signal. Two-three or four wire operation. Ranges from 0.1" water column. Accurate within ±2% span.

Series 603ASeries 603A

Dwyer Series 603A Differential Pressure Transmitters combine ultra low ranges, low cost, high accuracy and rugged construction - ideal for a wide range of HVAC and industrial applications. Utilizing a strain gage transducer in conjunction with the proven mechanical design of the famous Dwyer Magnehelic® Differential Pressure Gages, these transmitters provide a standard 4-20 mA analog output signal in ranges as low as 0.1" w.c. The two/three/four wire model 603A is powered by 13-35 VDC (2, 3, or 4wire) or 18-26 VAC (4-wire) loop current. All electronics components are mounted on a tough, durable fiberglass reinforced epoxy circuit board. These rugged units can tolerate repeated over-pressure up to the maximum pressure limit without damage or the need for recalibration. Accuracy is ±2% of span (as stocked) in normal ambient temperatures.

The transmitter can be surface mounted or flush mounted in a 4 13/l6" (122 mm) diameter panel hole. Hardware is included for either option. Duplicate 1/8" NPTF pressure connections on side and back ease installation. Based on its unique combination of price and performance, The Series 603A transmitter is ideal for use in commercial and industrial energy management systems. Typical applications include control of variable speed fans and blowers as well as the positioning of system dampers. Continuous data on air velocities in ducts and air filter pressure drops can be fed to the controlling computer.

SPECIFICATIONS
GENERAL
Maximum Pressure: 35 PSIG (2.46 kg/cm2)
Media Compatibility: Air and non-combustible, non-corrosive gases
ELECTRICAL
Power Supply: 13-35 VDC - 2, 3 or 4 wire, 18-26 VAC - 4 wire
Connections: 4 screw terminal block
Output Signal: 4-20 mA DC (limited at 38 mA DC)
Loop Resistance: DC; 0-1100 ohms, AC- 0-1130 ohms
Warm-up Time: 10 minutes
Current Consumption: DC; 38 mA max., AC; 76 mA max.
MECHANICAL
Weight: 1 lb., 10 oz. (.74 kg)
Span and Zero Adjustments: External potentiometers
Pressure Connections: 1/8" NPT female
Materials: Die cast aluminum case, silicone diaphragm, acrylic cover
PERFORMANCE AT 70°F (21.1°C)
Zero Output: 4 mA DC
Full Span Output: 20 mA DC
Accuracy: (Includes linearity, hysteresis and repeatability) ±2% of full span output
Stability: ±1% F.S./year
ENVIRONMENTAL
Operating Temperature: 20-120°F (-6.7 to 49°C), dry air
Thermal Error: ±1%/50°F typical
STANDARD ACCESSORIES
Mounting ring, snap ring, (4) 6-32 x 1 1/4 round head machine screws (3) 6-32 x 5/16" round head machine screws, (2) adapters, 3/16" I.D. tubing 1/8" NPT pipe plugs and adjustment key for span and zero.

Optional 3 1/2 digit LCD readout is available for Series 603A, 630A and 632A transmitters. 1/2" liquid crystal display reads 0-100(%) of full span pressure. Plus or minus indication included. To order, add suffix LCD to model number. Example: 603A-4-LCD. For direct readings in PSI, in w.c., metric units, etc., specify with order. Example: 603A-4-LCD reading directly in pressure units, 0-5.0 in w.c.Series 603A

SERIES 603A TRANSMITTER MODELS & RANGES (2-3-4 WIRE)
Model Number Range in Inches of Water
As Stocked Min. Range Max. Range
603A-1
603A-2
603A-3
603A-4
603A-5
603A-6
603A-11
603A-12
603A-13
603A-14
0-0.25
0-0.50
0-2.0
0-5.0
0-25
0-100
.25-0-.25
1-0-1
5-0-5
10-0-10
0-.10
0-.35
0-1.5
0-4.0
0-20
0-50
0-.40
0-2.0
0-6.0
0-25
0-100
0-250
Ranges in PSI
603A-7
603A-8
0-20
3-15
0-5
0-25