Back To Previous PagePHONE NUMBER
Sitemap

Pressure Transmitter- Series 634E

4-20 mA signal. Two wire operation. Ranges to 6000 psi.

Series 634E Series 634E

Series 634E Transmitters sense a single pressure of air, compatible gas or liquid and produce a standard 4-20 mA output signal Sensitive silicon strain gage measures within ±2% F.S.O. Convenient 2-wire operation simplifies installation and expands application versatility over comparable 3 or 4-wire units. Zero and span adjustments are fully protected inside a rugged die cast aluminum housing with durable gray polyurethane finish. Enclosure is designed to meet NEMA 4X requirements.

PHYSICAL DATA.
GENERAL
Maximum Pressure: 1.5 x maximum range
Media Compatibility: Air and non-corrosive gases and liquids
Housing: Designed to meet NEMA-4X
ELECTRICAL
Power Supply: 12.3 to 35 VDC
Output Signal: 4-20 mA DC, 2 wire (limited at 39 mA maximum)
Loop Resistance: 0-1135 ohms from 12.3 to 35 VDC
Current Consumption: DC: 38 mA max.
MATERIALS
Die cast aluminum with textured gray polyurethane finish, beryllium copper Bourdon tube, brass pressure connection.
MECHANICAL
Weight: 1 lb., 12 oz. ( 0.8 kg)
Span and Zero Adjustments: Protected potentiometers, located in auxiliary housing
Pressure Connection: ¼" NPTF x ½" NPTM
PERFORMANCE AT 70°F (21°C)
Zero Output: 4 ma DC
Full Span Output: 20 mA DC
Accuracy: ±2% of full span output.
Span and Zero: Adjustable to 0.05% of full span
Warm-up Time: 10 minutes
ENVIRONMENTAL
Operating Temperature: 20 to 120°F (-6.7 to 48.9°C)
Thermal Errors: ±1% per 50°F (27.8°C) typical
STANDARD ACCESSORIES
Three (3) "Z" mounting brackets
Three (3) 10-32 x ¼" RH machine screws
MODULE MODELS
Model Number Ranges in PSI
As Stocked Min. Range Max. Range
634E-0
634E-1
634E-2
634E-3
634E-4
634E-5
0-10
0-30
0-100
0-500
0-1000
0-2000
0-5
0-20
0-50
0-200
0-800
0-1500
0-20
0-60
0-200
0-800
0-2000
0-6000