Back To Previous PagePHONE NUMBER
Sitemap

Temperature Transmitter- Series 650

4-20 mA signal. Two wire operation.Temperatures from -55° to +180°C.

Series 650 Series 650

The Dwyer Series 650 Temperature Transmitter combines low cost with small size making it ideal for a wide variety of HVAC, industrial and commercial multi-point temperature monitoring applications. Non-polarized terminals simplify connection to any 12-35 VDC power supply. Capable of operation with long cable runs, Series 650 Transmitters are well suited for monitoring air or water temperatures at remote locations. Three models are stocked in popular ranges factory calibrated within 0.3% of span. All are linear within 0.25% of span and may be recalibrated within low range and span limits shown in chart. Low Range is temperature corresponding to 4 mA output. Span is temperature difference between Low and High Ranges corresponding to 4-20 mA output signal. Refer to Bulletin E-62 for complete details.

SERIES 650 TRANSMITTER MODELS AND RANGES





Model Number Range
As Stocked
Low Range Limits T/C Type, Range
Min. Max. Min. Max.
650-1 -23° to +10°C -32°C -14°C 24°C 48°C
650-2 -7° to +49°C -12°C +6°C 37°C 150°C
650-3 0° to +100°C
Consult factory for special ranges calibrated within the limits of -55°C and +180°C.

PHYSICAL DATA.



Power Supply: 12-35 volts DC
Output Signal: 4-20 mA DC
Voltage Stability: Output error less than 0.01% of span over the specified supply voltage range
Linearity: Within 0.25% of span
Thermal Drift: Less than 0.5% of span over ambient temperature range of 0 to 50°C (32 to 122°F)
Ambient Operating Temperature
(Electronics):
0 to 70°C (32 to 158°F)
Maximum Temperature (Probe): 204°C (400°F)
Probe Construction: 6" long, 0.25" O.D. Type 304 Stainless Steel
Probe Cable Length: 7 feet
Initial Calibration: Within 0.3% of span at 20°C (68°F) ambient


- © FLW, Inc 1997- - S.D.G.