The Dwyer Series 8500 Temperature/Process Control provides an impressive selection in a compact, economical 1/8 DIN package. Choose from two case styles in horizontal or vertical formats. Features include on-off, time proportioning, proportional, PI, PD or full PID control - fully programmable from the front panel - or use Self-Tune® PID. Inputs are selectable from a variety of thermocouple types including J, , T, E, N or L; DIN NIST or Ni RTD's. Output choices include solid state relay, mechanical relay, 5 VDC - ideal for driving an external SSR - or isolated 4-20 mA proportional current. An optional programmable alarm provides a full array of alarm action configurations including high alarm, low alarm and high/low guardband alarm. Manual reset, power-up inhibit and power interrupt reset provide additional alarm flexibility.
A water and corrosion resistant front panel (NEMA 4X, IP65), input fault timer, digital input filter, Self-Tune® ramp to setpoint, four password protected security levels and °F or °C display selection are all standard. Entire electronics package is easily field replaceable without wiring changes thanks to the removable front panel.
| Input Impedance: | Thermocouple + 3 megohms minimum, RTD current = 200 A maximum |
|---|---|
| Sensor Break or Short Protection: | De-energizes control output to protect system |
| Setpoint Range: | Selectable |
| Display: | Two 4 digit, 7 segment LED; 0.4" (10 mm) high - horizontal models; 0.3" (7.62 mm) high -vertical models |
| Control Action: | Selectable for Reverse (usually heating) or Direct (usually cooling) |
| Accuracy: | ±0.25% of span, ±1 degree |
| Resolution: | 1 degree or 0.1 degree |
| Temperature Stability: | 2.3 V/°F (4 V/°C) typ., 4.5 V/°F (8 V/°C) maximum |
| Common Mode Rejection: | 140 db minimum at 60 Hz |
| Normal Mode Rejection: | 65 db typical, 60 db at 60 Hz |
| Isolation: | Relay and SSR outputs; 1500 VAC. 0-20 mA output; 500 VAC. 5 VDC output is not isolated |
| Power Consumption: | 5 VA maximum |
| Supply Voltage: | 100 to 240 VAC nominal, +10%-15%, 50 to 400 Hz, single phase; 132 to 240 VDC +10%-20% |
| Operating Temperature Range: | 14 to 131°F (-10 to 55°C) |
| Storage Temperature Range: | -40 to 176°F (-40 to 80°C) |
| Humidity Range: | 0 to 90% up to 104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) |
| Memory Backup: | Non-volatile memory. No batteries required |
| Control Output Ratings: | SSR: 2.5 A at 240 VAC resisting at 77°F (25°C). De-rate to 1.25 A at 130°F (55°C) Relay: SPDT, 10 A at 240 VAC resistive Alarm Relay: SPST, 3 A at 240 VAC resistive Switched Voltage (non-isolated): 5 VDC at 20 mA Proportional Current: 0-20 mA DC, scaleable into 600 ohms maximum. |
| Weight: | 10 oz. (369 g) |
| Model No.1 | Alarm | Input | Output 2 |
|---|---|---|---|
| D85011-(1)(0) D85012-(1)(0) D85013-(1)(0) D85015-(1)(0) D85021-(1)(0) D85022-(1)(0) D85023-(1)(0) D85025-(1)(0) D85111-(1)(0) D85112-(1)(0) D85113-(1)(0) D85115-(1)(0) D85121-(1)(0) D85122-(1)(0) D85123-(1)(0) D85125-(1)(0) |
No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes |
Thermocouple Thermocouple Thermocouple Thermocouple RTD RTD RTD RTD Thermocouple Thermocouple Thermocouple Thermocouple RTD RTD RTD RTD |
SSR 5 VDC Relay 4-20 mA SSR 5 VDC Relay 4-20 mA SSR 5 VDC Relay 4-20 mA SSR 5 VDC Relay 4-20 mA |
1 Specify suffix 1 for horizontal or 0 for vertical mounting. 2 When ordering a control to operate contractor or solenoid loads greater than 100 mA, select the SSR output instead of the Relay. If the relay is selected, order part number A-600. R/C snubber. |
|||
SUGGESTED SPECIFICATIONS :
Process Controller shall be microprocessor based of 1/8 DIN size with dual four digit LED displays and accuracy of �0.25% of span, �1 least significant digit. PID control will Self-Tune� automatically and Fuzzy Logic software shall be included. Selectable inputs and associated impedance to be thermocouple (3 megohms min.), RTD current (200mA max.), current (10 ohms) and voltage (5000 ohms). Sealed front panel shall have NEMA 4X (IP 65) rating. Outputs shall be selectable for relay logic, current, voltage or switched voltage. Electronics replaceable without wiring changes via removable front panel. Process controller shall be Dwyer Model D86 _____.