Back To Previous PagePHONE NUMBER
Sitemap

Immersion Temperature Control- Series FM

Visible setpoint adjustment, adjustable deadband

Series FM Series FM

Compact and low cost, model FM-437 employs a bimetal element inside an immersion well. Instrument is detachable form the well, allowing maintenance without draining system. Visible calibrated dial reduces "start up" time and speeds set point changing. Contacts are hermetically sealed and mercury wetted. High current (up to 17A) capacity switches available on special order.

PHYSICAL DATA.

Maximum Pressure: Copper well - 200 psig @ 300°F
304SS well - 900 psig @ 300°F
Maximum Bi-Metal Temperature: 375°F
Process Connection: ¾" NPT
Electrical Rating: 4A @ 120V, 2A @ 240V, both AC & DC, 1/8 HP @ 120VAC or 240VAC.
Switch Type: Tilting mercury type
Wiring Connections: Three screw type: common, normally open and normally closed. (SPDT)
Conduit Opening: ½ inch conduit
Set Point Adjustment: High and Low set points set via pointers on (°F) calibrated dial
Housing: Heavy gauge steel case with glass window
Well Material: Copper or Type 304 stainless steel - see chart
Weight: 3 lbs.
Installation: Well must be horizontal, window vertical

FACTORY STOCKED MODELS

Cooper Well
Model Number
Type 304SS Well
Model Number
Operating
Temperature Range
Deadband Well Dimension
Min Min a b
FM-437-153-3515
FM-437-153-3516
FM-437-153-3510
FM-437-153-3511
FM-437-153-3528
FM-437-153-3529
FM-437SS-153-3515
FM-437SS-153-3516
FM-437SS-153-3510
FM-437SS-153-3511
FM-437SS-153-3528
FM-437SS-153-3529
40-200°F
40-200°F
80-240°F
80-240°F
160-300°F
160-300°F
15
15
15
15
18
18
160
160
160
160
140
140
2 7/8"
4 ½"
2 7/8"
4 ½"
2 7/8"
4 ½"
2 3/8"
¾"
2 3/8"
¾"
2 3/8"
¾"

SUGGESTED SPECIFICATIONS
Temperature switches shall be immersion type with (copper)(type 304 stainless steel) well. Switches shall be separable from well and shall be repairable without shutting down process. Bimetal element shall operate hermetically sealed mercury switch. Switches shall have °F calibrated dial and two pointers indicating set and reset points. Switches shall require no power supply. Switches shall be Mercoid Model No. FM-437-(___).

- © FLW, Inc 1997- - S.D.G.