Precision FlowTM Air Velocity Transmitter- Series PF

High Accuracy, 0.2 Second Response, 4 to 20 mA Output

series PF Series PF

Precision Flow Air Velocity Transmitters directly monitor gas mass flow rates of free air flows or single point flows in pipes, ducts and stacks. The 4-20 mA output signal is linearly proportional to gas mass velocity without additional compensation needed for pressure and temperature variations. The 304 SS insertion probe contains a velocity sensor to monitor mass flow and a temperature sensor to automatically correct for temperature changes. The probe is directly mounted to a NEMA 2 anodized aluminum enclosure. Stocked models are calibrated for air.


Model Number Range
PF1300202
PF1300204
PF1300206
0 to 2000 SFPM
0 to 4000 SFPM
0 to 6000 SFPM

APPLICATIONS
Heating, ventilation and air conditioning (HVAC); hood and gas cabinet monitoring; cleanroom and cleanbench face velocity monitoring.

PHYSICAL DATA


Accuracy:
Repeatability:
Response Time:
Gas Pressure: 
Gas Temperature:
Supply Voltage:
Output:
Loop Resistance:
Operating Temperature:
Wetted Parts:
Storage Temperature:
Probe Dimensions:
Electrical Connections:
Weight:
±1% FS, ±0.5% of reading over 32 to 122°F ( 0 to 50°C) and 5 to 31 psia (0.35 to 2 kg/cm2)
±0.2% of F.S.
0.2 seconds to 63% of final velocity value
150 psig (10 kg/cm2 G) maximum
-40 to 250°F (-40 to 121°C)
15 to 18 VDC, 300 mA maximum
4 to 20 mA, linear
400 Ω maximum
32 to 122°F (0 to 50°C)
304 SS probe, glass coated sensor, epoxy
32 to 158°F (0 to 70°)
¼" (6.35 mm) O.D., 13" (33cm) length
Four wire standard connector
0.0 lbs. (0.30 kg)

SUGGESTED SPECIFICATIONS
Air velocity transmitter shall be an insertion type mass flow meter with accuracy of ±1% FS, +0.5% of reading and a 0.2 second response time. Transmitter shall provide a 4-20 mA output signal linearly proportional to gas mass velocity. Insertion probe shall be constructed of 304 SS with a glass coated sensor assembly. Electronics shall be housed in a NEMA 2 enclosure. Air velocity transmitter shall be Dwyer Model No, PF _____.

- © FLW, Inc 1997- - S.D.G.