Series SC Limit Alarmsare ideal for indicating production line faults, process upsets, equipment failures, or control system abnormalities. Units accept DC, RTD, or thermocouple input and provide independent SPDT relay output per setpoint. Limit alarms feature programmable HI or LO and failsafe or non-failsafe adjustable setpoints. Bright LEDs indicate line power, input signal status and relay state.
| Relay Output: | 2 SPDT, one relay per setpoint, 5A @ 120 VAC resistive |
|---|---|
| Isolation: | 1800 VDC between contacts, input, and power |
| Setpoints: | Dual, adjustable from 0 to 100% of span |
| Stability: | ±0.05% full scale/°C |
| Repeatability: | (SC601)>0°C: 0.2%, (SC713) ±0.2% FS, (SC823)>50 mV/5 mA: 0.1% FS |
| Deadband: | (SC601) 0.2505%, (SC713) 1.0-5%, (SC823)>50 mV/5 mA: 0.25-5% |
| Response Time: | 250 msec normal mode |
| Input Impedance: | (SC601)>1 MΩ, (SC823) Voltage: 10Ω Current:>100kΩ |
| Thermocouple Burnout Detect: | (SC601) configurable upscale, downscale, or disabled |
| Ambient Operating Temperature: | 32 to 131°F (0 to 55°C) |
| Storage Temperature: | -13 to 158°F (-25 to 70°C) |
| Power Supply: | 9 to 30 VDC |
| Power Consumption: | 1.5 W typical, 2.5 W maximum |
| Electrical Connections: | Screw terminal for 12-22 AWG |
| Model Number | Input Type |
|---|---|
| SC601 | Type J, K, T, R, S, E, B Thermocouple |
| SC713 | Pt100 Ω, Pt 1000Ω, Cu10, Cu100, Ni120, NiFe604 RTDs, 3-wire |
| SC823 | 10mV to ±200 V DC voltage input, 1 mA to ±100 mA DC current input |