Back To Previous PagePHONE NUMBER
Sitemap

Sig-Con™ Limit Alarms- Series SC

DC, RTD or Thermocouple Input,Configurable Ranges

Series SCSeries SC

Series SC Limit Alarmsare ideal for indicating production line faults, process upsets, equipment failures, or control system abnormalities. Units accept DC, RTD, or thermocouple input and provide independent SPDT relay output per setpoint. Limit alarms feature programmable HI or LO and failsafe or non-failsafe adjustable setpoints. Bright LEDs indicate line power, input signal status and relay state.

PHYSICAL DATA.

Relay Output: 2 SPDT, one relay per setpoint, 5A @ 120 VAC resistive
Isolation: 1800 VDC between contacts, input, and power
Setpoints: Dual, adjustable from 0 to 100% of span
Stability: ±0.05% full scale/°C
Repeatability: (SC601)>0°C: 0.2%, (SC713) ±0.2% FS, (SC823)>50 mV/5 mA: 0.1% FS
Deadband: (SC601) 0.2505%, (SC713) 1.0-5%, (SC823)>50 mV/5 mA: 0.25-5%
Response Time: 250 msec normal mode
Input Impedance: (SC601)>1 MΩ, (SC823) Voltage: 10Ω Current:>100kΩ
Thermocouple Burnout Detect: (SC601) configurable upscale, downscale, or disabled
Ambient Operating Temperature: 32 to 131°F (0 to 55°C)
Storage Temperature: -13 to 158°F (-25 to 70°C)
Power Supply: 9 to 30 VDC
Power Consumption: 1.5 W typical, 2.5 W maximum
Electrical Connections: Screw terminal for 12-22 AWG
FACTORY STOCKED MODELS

Model Number Input Type
SC601 Type J, K, T, R, S, E, B Thermocouple
SC713 Pt100 Ω, Pt 1000Ω, Cu10, Cu100,
Ni120, NiFe604 RTDs, 3-wire
SC823 10mV to ±200 V DC voltage input,
1 mA to ±100 mA DC current input

- © FLW, Inc 1997- - S.D.G.