Self-Acting Temperature Control Valves- Series 36R

Direct-Acting - Reverse-Acting

Series 36R Series 36R
Series 36R
Temperature X
In. (mm)
Y
In. (mm)
Z
In. (mm)
Hub
Low Ranges 17
(431.8)
7/8
(22.2)
20 3/16
(512.8)
1" NPT
High Ranges 6 1/2
(165.1)
3/4
(19.1)
9 1/2
(241.5)
1" NPT

W.E. Anderson Series 36R Self-Acting Temperature Control Valves feature self-contained valve, actuator and sealed thermal system in one compact unit providing instillation economy and long term reliability. Available wither Direct-Acting (valve closes on temperature rise ) or Reverse-Acting (valve opens on temperature rise), quick-opening double seated valve enables fast response for improved process control. Request Bulletin F-24N for valve sizing nomographs for liquids and steam.

HOW TO APPLY


  1. Select Model No. to specify pipe size and control action.
  2. Specify operating temperature range selected from chart below. Consult factory with operating perimeters for non-standard Temperature Control Valve requirements.
STANDARD MODELS


PIPE SIZE MODEL ACTION A IN. (MM) B IN. (MM) C IN. (MM)
1/2" 36RJ131 DIRECT-ACTING 3 1/16 (77.8) 1 1/16 (27.0) 2 21/32 (67.5)
36RK131 REVERSE-ACTING 4 (101.6) 2 (50.8) 1 7/8 (47.6)
3/4" 36RJ231 DIRECT-ACTING 3 1/2 (88.9) 1 7/32 (31.0) 2 21/32 (67.5)
36RK231 REVERSE-ACTING 4 (101.6) 2 (50.8) 1 7/8 (47.6)
1" 36RJ331 DIRECT-ACTING 4 1/4 (108.0) 1 13/32 (35.7) 3 3/16 (81.0)
36RK331 REVERSE-ACTING 4 3/8 (111.1) 2 1/8 (54.0) 2 (50.8)
1 1/4" 36RJ431 DIRECT-ACTING 4 3/4 (120.7) 1 21/32 (42.1) 3 7/32 (81.8)
36RK431 REVERSE-ACTING 4 1/2 (114.3) 2 1/4 (57.2) 2 1/4 (57.2)
1 1/2" 36RJ531 DIRECT-ACTING 5 1/4 (133.4) 1 29/32 (48.4) 3 21/32 (92.9)
36RK531 REVERSE-ACTING 5 1/2 (139.7) 2 1/2 (63.5) 2 3/4 (69.9)
2" 36RJ631 DIRECT-ACTING 6 9/16 (166.7) 2 1/2 (63.5) 5 3/16 (131.8)
36RK631 REVERSE-ACTING 7 1/4 (184.2) 3 3/4 (95.3) 4 1/8 (104.8)

PHYSICAL DATA


CONNECTIONS
Body 1/2" NPT to 2" NPT
Thermal System Hub 1" NPT-17" (431.8mm) bulb; 1" NPT- 6 1/2" (165.1 mm) bulb
WETTED MATERIALS
Body Bronze
Stuffing Box 316 SS
Trim Nickel Alloy
Packing Graphite
Bulb and Capillary 304 SS with spirally wound armor
OTHER MATERIALS
Chassis Aluminum
Spring Plated spring steel
Bellows Beryllium Copper/Brass
Thermal System Connections 303 SS/304 SS
MAXIMUM PRESSURE 150 psi (10.5 kg/cm2) MAXIMUM TEMPERATURE: 400°F (204°C)
OPERATING TEMPERATURE RANGES See chart above
OPTIONS Split flange, oversize hub and well thermal system connections, 316SS bodies, single-seated valves with 316SS trim and Teflon packing, restricted trim or needle plugs, graphite packing lubricators.

STANDARD OPERATING TEMPERATURE RANGES

Controller Range °F(°C) Bulb-X
in. (mm)
Sensitivity
Low Medium High
10°-65°F (-12°-18°C)
40°-100°F (4°-38°C)
70°-145°F (21°-63°C)
110°-170°F (43°-77°C)
130°-190°F (54°-88°C)
170°-240°F (77°116°C)
220°-275°F (104°-135°C)
270°-340°F (132°-171°C)
17 (431.8)
17 (431.8)
17 (431.8)
6 1/2 (165.1)
6 1/2 (165.1)
6 1/2 (165.1)
6 1/2 (165.1)
6 1/2 (165.1)
16° (8.9°)
14° (7.8°)
16° (8.9°)
17° (9.4°)
17° (9.4)
16° (8.9°)
14° (7.8°)
15° (8.3°)
13° (7.2°)
13° (7.2)
14° (7.8°)
14° (7.8°)
14° (7.8°)
16° (8.9°)
13° (7.2°)
14° (7.8°)
12° (6.7°)
11° (6.1°)
12° (6.7°)
13° (7.2°)
12° (6.7°)
14° (7.8°)
12° (6.7°)
12° (6.7°)

*Sensitivity data applies to a 1" size value.

SUGGESTED SPECIFICATIONS
Self-Acting Temperature Control Valve shall be (Direct-Acting) (Reverse-Acting) providing for valve (closure) (opening) on rise in temperature. Valve body shall be Bronze and Trim shall be precision machined Nickel Alloy for durability and corrosion resistance. Valve shall be double seated and quick opening for fast response. Self-contained thermal system shall include: 304SS bulb with 18" flexible extension; 10 ft. length of 304SS capillary with spirally wound armor; and stainless steel union connection with hub for instillation flexibility. Self-Acting Temperature Control Valve shall be W.E. Anderson Model No.______, Range______.

- © FLW, Inc 1997- - S.D.G.