• Features
  • Ordering Information
  • Specifications
  • Loop-powered
  • 1 Volt Drop
  • FM Approved (PD682)
  • Easy 2 Step Non-interactive Calibrations
  • 4-20 mA Input
  • 3-1/2 Digit + Extra Zero LCD Display +/- 19,99(0)
  • 0.5" High LCD Display
FM PD682 only
Model PD682 photo
Model: Description:
   *PD682 FM Approved Loop-powered Panel Meter
   PD680 Loop-powered Panel Meter
   PDA2405 NEMA 4X Front Panel

See also: Precision Digital Enclosures
APPROVAL: FM approved as intrinsically safe with entity, for use in Class I, Division 1, Groups A,B,C,D hazardous locations, and Class II and III, Division 1, Group E,F,G hazardous locations when installed in Precision Digital enclosures PDA2407, PDA2408, PDA2409 or PDA2410.

Nonincendive for use in Class I, Division 2, Group A,B,C,D hazardous locations when installed in an enclosure capable of accepting one of the Division 2 wiring methods specified in the National Electric Code (NFPA 70), including Precision Digital enclosures PDA2407, PDA2408, PDA2409 or PDA2410. Suitable for use in Class II and III, Division 2, Group F,G hazardous locations when installed in Precision Digital enclosures PDA2407, PDA2408, PDA2409 or PDA2410.
  • MAX. ENTITY PARAMETERS: Vmax = 30 V, Imax = 175 mA, Ci = 0, Li = 0
  • OPERATING TEMPERATURE: 0oC to 70oC (32oF to 158oF)
  • ENCLOSURE: 1/8 DIN
  • CONNECTIONS: Removable screw terminal block.
Hazardous Area Approval Explanations
INTRINSIC SAFETY: This method of protection limits the energy passing into the hazardous area. The energy limitation is provided by the use of safety barriers which are mounted in the safe area. Because of the energy limitation, regardless of the fault in the hazardous area, sufficient energy cannot be released to ignite the explosive atmosphere.

Approval Methods: There are two methods used by approval authorities to assure an intrinsically safe system:
System Approval: The system approval method is one in which specific field devices are examined in combination with specific barriers. No other field device or barriers may be substituted unless specifically examined by the approval authority.
Entity Approval: The entity approval method is one in which each piece of equipment is evaluated separately and assigned a set of safety parameters. The field device may then be connected to a barrier with compatible safety parameters.
NONINCENDIVE: A device may be installed in Division 2 locations if it has been approved as nonincendive. Nonincendive equipment is incapable of releasing sufficient electrical or thermal energy to ignite flammable gases or vapors under "NORMAL" operation and environmental conditions. Nonincendive devices need no special enclosure or other physical safeguard.

EXPLOSION PROOF: This is the most popular method of protection. When an explosive gas enters an enclosure containing electrical equipment an explosion could occur. With the enclosure properly installed, and the tight tolerance between the enclosure and the cover, the flame will cool sufficiently by the time it reaches the outside atmosphere.
2 or 4 Relays
  • 2 or 4 SPDT, 2 amps @ 250 VAC Resistive Load
  • Automatic or Automatic + Manual Reset
  • Failsafe Action & Auto Initialization
  • 0-100% Deadband Adjustment
Isolated 4-20 mA Transmitter Output
  • 4-20 mA or 20-4 mA Output
  • 500 VDC Isolation
  • Can be Scaled over Narrow Range
  • With or Without Relay Contacts
The PD750, equipped with the isolated 4-20 mA output signal option turns the unit into a temperature transmitter with a digital display. This 4-20 mA signal is linearized, cold junction compensated and may be scaled for practically any range.
  • PD750 Four Wire RTD Connections
  • PD750 Three Wire RTD Connections
  • PD750 TwoWire RTD Connections
  • PD750 Thermocouple Connections
PD750-3-15.jpg (9182 bytes)
Pre-calibrated Ranges
Input: Range: Accuracy:
Type J -328o to 1382oF
-200o to 750oC
+/-1.4oF
+/-0.8oC
Type K -328o to 2498oF
-200o to 1330oC
+/-1.7oF
+/-0.9oC
Type T -328o to 2498oF
-200o to 750oC
+/-1.5oF
+/-0.8oC
Type E -328o to 2498oF
-200o to 750oC
+/-1.4oF
+/-0.8oC
Type R -328o to 2498oF
-200o to 750oC
+/-4.8oF
+/-2.7oC
Type S -328o to 2498oF
-200o to 750oC
+/-5.7oF
+/-2.9oC
100 ohm Pt RTD -328o to 2498oF
-200o to 750oC
+/-0.6oF
+/-0.3oC
10 ohm Cu RTD -328o to 2498oF
-200o to 750oC
+/-0.2oF
+/-0.1oC
120 ohm Ni RTD -328o to 2498oF
-200o to 750oC
+/-0.2oF
+/-0.1oC