• Features
  • LED Status Indication
  • Ordering Information
  • Specifications
Universal mV Meter(Model PD691)
  • 0-30 mV, 0-200 mV, +/-15 mV, +/-100 mV Field Selectable Inputs
  • 5, 10 or 24 VDC Field Selectable Excitation Power Supply
  • Easy Single Button Scaling with Lockout Feature
  • 11 Point Linearization
  • Peak Hold Feature
  • Capture or Programmable Tare Feature
  • Steady, Accurate Display to +/-199,990
  • NEMA 4X Front Panel
  • 4 Visual Alarm Points with Front Panel LED Status Indication
  • 2 or 4 Relays + 4-20 mA Output Options
Universal mV Meter(Model PD691)
A green LED labeled "T" illuminates when the PD691 displays a tared value and a green LED labeled "P" illuminates when the PD691 displays a peak value
Ordering Information(Model PD691)
Model: Description:

115 VAC
*PD691-3-N No Options
*PD691-3-14 2 Relays
*PD691-3-15 4-20 mA Output
*PD691-3-16 2 Relays + 4-20 mA Output
*PD691-3-17 4 Relays
*PD691-3-18 4 Relays + 4-20 mA Output
230 VAC
PD691-4-N No Options
PD691-4-14 2 Relays
PD691-4-15 4-20 mA Output
PD691-4-16 2 Relays + 4-20 mA Output
PD691-4-17 4 Relays
PD691-4-18 4 Relays + 4-20 mA Output
 
Note: A -G may be added at in the part number to call out meters with a green display, ex. PD691-3G-14
Note 2: The PD691 can be modified to have the external acknowledge terminal to become an external TARE terminal, contact Leighton Stone Corporation for details.
Basic Meter
  • INPUTS: Field selectable, 0-30 mV, 0-200 mV, +/-15mV, +/-100mV.
  • DISPLAY: Bright, large, 0.56" (14.2mm) high efficiency red or green LED. 4-1/2 digits + extra zero; +/-19999(0).
  • ISOLATED POWER SUPPLY: Selectable 5 or 10 VDC +/-5% @ 50 mA; or 24 VDC +/-5% @ 20 mA. Available for either strain gauge or 4-20 mA output option.
  • PEAK HOLD: Captures the peak reading and displays it via the front panel ENTER button.
  • PEAK HOLD INDICATION: Front panel LED.
  • TARE: 2 Modes,
    • Capture - Sets a currently displayed reading to zero via front panel TARE button and may be reset at any time.
    • Programmable - Automatically subtracts a user selected tare value from the actual reading.
  • TARE INDICATION: Front panel LED.
  • ACCURACY: 0.05% of full scale, +/-1 count. Non-volatile Memory: All programming values are stored in non-volatile memory for ten years if power is lost.
  • LOCKOUT: Dip switch restricts modification of calibration values.
  • POWER: 115 VAC or 230 VAC +/-10%, 50/60 Hz, 10 VA.
  • ENCLOSURE: 1/8 DIN, high impact plastic, UL 94V-0.
  • FRONT PANEL: NEMA 4X, panel gasket provided.
  • CONNECTIONS: Removable screw terminal block (provided).
  • ALARM POINTS: 4, any combination of high or low alarms.
  • ALARM STATUS INDICATION: Front panel LED.
  • ALARM DEADBAND: 0-100% of full scale, user selectable.
  • UL FILE NUMBER: E160849; 508 Industrial Control Equipment.
Relays
  • RATING: 2 or 4 relays; SPDT (form C). The contacts are rated 2 Amp @ 30 VDC or 2 Amp @ 250 VAC resistive load; 1/14 HP @ 125 / 250 VAC for NC contacts and 1/10 HP @ 125 / 250 VAC for NO contacts, inductive load.
  • RESET: User select. 1. Automatically when the input passes the reset point. 2. Automatically + manually (via user supplied switch).
  • FAILSAFE OPERATION: The relay coils are energized in the non-alarm condition. In the case of a power failure, the relays will go to the alarm state. May be disabled with internal jumper.
  • AUTO INITIALIZATION: When power is applied to the meter, the relays will always reflect the state of the input to the meter.
  • DEADBAND: 0-100%, User Selectable.
Isolated 4-20 mA Transmitter Output
  • CALIBRATION RANGE: Anywhere in range of meter, 501 count minimum span.
  • OUTPUT LOOP RESISTANCE:
Loop Resistance
Power Supply Min Max
24 VDC 10 ohm 600 ohm
36 VDC (external) 600 ohm 1000 ohm
 
  • ACCURACY: +/-0.1% FS, +/-.004 mA
  • ISOLATION: 500 VDC or peak AC, input-to-output or input/output-to-power line.
  • EXTERNAL LOOP POWER SUPPLY: 35 V max.