• Features
  • Ordering Information
  • Specifications
Universal Process Meter(Model PD690)
  • Easy Single Button Scaling with Lockout Feature
  • 4-20 mA, 0-5 V, or 0-10 V Field Selectable Inputs
  • 24 V Transmitter Power Supply Standard
  • Stand Alone Scaling
  • Steady, Accurate Display to +/- 199,990
  • 11 Point Linearization
  • Square Root Extraction
  • 4-1/2 Digit + Extra Zero
  • NEMA 4X Front Panel
  • 2 or 4 Relay + 4-20 mA Output Options
  • Isolated 18-36 VDC Powered Option
  • Green Display Available
  • Easy Setup Instructions on Meter
Ordering Information(Model PD690)
Model: Description:

115 VAC
*PD690-3-N No Options
*PD690-3-14 2 Relays
*PD690-3-15 4-20 mA Output
*PD690-3-16 2 Relays + 4-20 mA Output
*PD690-3-17 4 Relays
*PD690-3-18 4 Relays + 4-20 mA Output
230 VAC
PD690-4-N No Options
PD690-4-14 2 Relays
PD690-4-15 4-20 mA Output
PD690-4-16 2 Relays + 4-20 mA Output
PD690-4-17 4 Relays
PD690-4-18 4 Relays + 4-20 mA Output
18-36 VDC
PD690-2-N No Options
PD690-2-14 2 Relays
PD690-2-15 4-20 mA Output
PD690-2-16 2 Relays + 4-20 mA Output
PD690-2-17 4 Relays
PD690-2-18 4 Relays + 4-20 mA Output
 
* Quick Shipment Item, shipped within two working days
 
Most other products shipped within one week, call for best shipping date.
Note: A -G may be added in the part number to call out meters with a green display ex. PD690-3G-14;
Options:
Model: Description:

PD174 2 Relay Option (-14 in P/N)
PD175 4-20 mA Output Option (-15 in P/N)
PD176 2 Relays + 4-20 mA Output (-16 in P/N)
PD177 4 Relays Output Option (-17 in P/N)
PD178 4 Relays + 4-20 mA Output (-18 in P/N)
PDX-6901 Snubber
Basic Meter
  • INPUTS: Field selectable, 4-20 mA, 1-5 V, 0-5 V, 0-10 V.
  • DISPLAY: Bright, Large, 0.56" (14.2mm) high efficiency red or green LED. 4-1/2 digits + extra zero; +/- 19999(0), (0) may be switched on to display 199,990.
  • FRONT PANEL: NEMA 4X, panel gasket provided.
  • CALIBRATION: May be calibrated using internal calibration (I-CAL) or by applying an external calibration signal (E-CAL).
  • CALIBRATION RANGE: 4 mA (1V) input may be set to display anywhere in range of meter. 20 mA (5V) may be set anywhere above or below 4 mA input. Non-volatile Memory: All programming values are stored in non-volatile memory for ten years if power is lost.
  • LOCKOUT: Jumper 3 at rear of instrument restricts modification of calibration values.
  • LOOP POWER: (AC powered units only) Isolated 24VDC at 20 mA regulated. Noise less than 10 mV p-p. Max loop resistance of 1200 ohms. Available for either signal input or 4-20 mA output option, but not both.
  • HOLD READING: Connect terminals HLD and COM.
  • ACCURACY: 05% of calibrated span.
  • INPUT IMPEDANCE: Voltage ranges, greater than 300 Kohms; Current range, 100 ohms.
  • POWER: AC power: 115 VAC +/- 10%, 50/60 Hz, 10VA. 230 VAC +/- 10%, 50/60 Hz, 10VA. DC power: 18-36 VDC, 6 watts max.
  • ISOLATION: AC power: 1500 VAC; DC power: 500 VDC.
  • ENVIRONMENTAL: Operating temperature range: 0 to 65¡C. Storage temperature range: -40 to 85ûC. Relative Humidity: 0 to 90% non-condensing.
  • ENCLOSURE: 1/8 DIN, high impact plastic, UL 94V-0.
  • CONNECTIONS: Removable screw terminal block (provided).
  • ALARM POINTS: 4, any combination of high or low alarms.
  • ALARM STATUS INDICATION: Front panel LED.
  • ALARM DEADBAND: 0-100%, User Selectable.
  • UL FILE NUMBER: E160849; 508 Industrial Control Equipment.
Relays
  • RATING: 2 or 4 relays; 2 Amp SPDT (form C). The contacts are rated 2 Amp @ 30 VDC or 2 Amp @ 250 VAC resistive load; 1/14 HP @ 125 / 250 VAC for NC contacts and 1/10 HP @ 125 / 250 VAC for NO contacts, inductive load.
  • RESET: User Select. 1. Automatically when the input passes the reset point. 2. Automatically + manually (via user supplied switch or front panel ACK button).
  • FAILSAFE OPERATION: The relay coils are energized in the non-alarm condition. In the case of a power failure, the relays will go to the alarm state. May be disabled with internal jumper.
  • AUTO INITIALIZATION: When power is applied to the meter, the relays will always reflect the state of the input to the meter.
  • DEADBAND: 0-100%, User Selectable.
Isolated 4-20 mA Transmitter Output
  • CALIBRATION RANGE: Anywhere in range of meter, 501 count minimum span.
  • OUTPUT LOOP RESISTANCE:
Loop Resistance
Power Supply Min Max
24 VDC 10 ohm 600 ohm
36 VDC (external) 600 ohm 1000 ohm
 
  • ISOLATION: 500 VDC or peak AC, input-to-output or input/output-to-power line.
  • EXTERNAL LOOP POWER SUPPLY: 35 V max.